2014 Locke Supply Co.

GAS VALVES & IGNITORS

STANDING PILOT APPLICATIONS Combination gas controls for use in 24 VAC, gas-fired, standing pilot appliances with capacities from 20 to 200 CFH.

A.G.A. Certified Capacity *

Pressure Regulator Setting

Inlet/ Outlet Size

Type of Gas

Locke#

Vendor#

cfh

m3/hr

In. wc

kPa

VR8200A2744 Supersedes VR8200A2132

L4526

½ x ½ 130

3.7

3.5

0.87 Natural

Locke Code 4526 includes: 1/2 in. x 3/8 in. reducer bushing; 39369014 bag assembly-3/4 in. straight flange with O ring, screws and wrench; and 393691 Natural to LP gas conversion kit; also includes 3/4 in. angle flange

DIRECT SPARK APPLICATIONS These universal electronic ignition gas controls are used in gas-fired appliances with capacities up to 150 cu ft/hour at 1 inch wc pressure drop (4.2 cu m/hour at 0.25 kPa) for natural gas. The VR8245M will operate with a direct spark (DSI), hot surface (HSI) or intermittent pilot ignition. The control includes a manual valve, two automatic operators, a pressure regulator, pilot adjustment, pilot plug and ignition adapter.

A.G.A. Certified Capacity @ cfh m3/hr

Pressure Regulator Setting Type Of Gas

Inlet/ Outlet Size

Type of Pressure Regulator

Locke#

Vendor#

In. wc kPa

L

VR8245M2530 Supercedes VR8205A2024

L4529

½x½ 150

4.3

3.5

0.87 Natural Standard

| HVAC

* Capacities based on 1,000 Btu/ft 3, 0.64 sp gr natural gas at 1 in. wc pressure drop (37.3 MJ/m 3, 0.64 sp gr natural gas at 0.25 kPa pressure drop). ** Use of ½" x a " in. reducer bushing reduces capacity to 130 cfh (3.7 m 3/hr.).

GAS VALVE

GAS VALVE

Locke# L9701

624775 HW# VR8215SGas Valve

Locke# L9700

921691 HW# VR9205Q Gas Valve

Credit: 405-631-9756

461

www.lockesuppl .com

Made with