2014 Locke Supply Co.

SPLIT SYSTEM R401A AIR CONDITIONERS

TSA AIR CONDITIONERS R410A SPLIT SYSTEM UNITS 60 HZ

Locke#

Model#

Tonnage Volt

L4352

TSA072S4S-Y

6

208/230

L4353

TSA090S4S-Y 7.5 208/230

L4354

TSA090S4S-G 7.5

460

L4355

TSA120S4S-Y 10

208/230

REPLACES THE R22 HS29 UNITS.

L4356

TSA120S4S-G 10

460

SPECIFICATIONS

Model Number

TSA072S4S-Y TSA090S4S-Y TSA090S4S-G TSA120S4S-Y TSA120S4S-G

Nominal Size - Tons

6

7.5

10

Liquid Line (o.d.) -- in. connection (sweat)

(1) 5/8

(1) 5/8

(1) 5/8

Suction Line (o.d.) -- in. connection (sweat)

(1) 1-1/8

(1) 1-1/8

(1) 1-3/8

L

Net face area - sq. ft. Outer Coil

29.3

29.3

29.3

| HVAC

Inner Coil

---

28.4

28.4

Condenser Coil

Tube diameter - in. (mm) & No. of rows

3/8 -1

3/8 - 2

3/8 - 2

Fins per inch

20

20

20

Diameter - in. (mm) & No. of blades

(1)24-3

(1) 24 - 4

(2) 24 - 3

Motor horsepower

(1) 1/3

(1)1/2

(2) 1/3

Condenser Fans

Cfm total air volume

5100

5600

8300

Rpm

1075

1075

1075

Watts

430

580

830

Refrigerant Charge

11 lbs. 0 oz.

16 Ibs. 0 oz.

17Ibs. 0 oz.

ELECTRICAL DATA Model Number

TSA072S4S-Y TSA090S4S-Y TSA090S4S-G TSA120S4S-Y TSA120S4S-G

Line Voltage data - 60 hz - 3 phase

208/230V

208/230V

460V

208/230V

460V

Recommended maximum fuse or circuit breaker size (Amps)

45

50

25

70

40

Minimum circuit ampacity

27

35

17

43

24

Compressors (1)

Rated load amps

19

25

12.2

30.1

16.7

Locked rotor amps

123

164

100

225

114

Condenser Coil Fan Motor (1 phase)

Full load amps (total)

2.4

3

1.5

2.4 (4.8)

1.3 (2.6)

Locked rotor amps

4.7

6

3

4.7 (9.4)

2.4 (4.8)

Ma n Office: 405-631-9701