2014 Locke Supply Co.
SPLIT SYSTEM R401A AIR CONDITIONERS
TSA AIR CONDITIONERS R410A SPLIT SYSTEM UNITS 60 HZ
Locke#
Model#
Tonnage Volt
L4352
TSA072S4S-Y
6
208/230
L4353
TSA090S4S-Y 7.5 208/230
L4354
TSA090S4S-G 7.5
460
L4355
TSA120S4S-Y 10
208/230
REPLACES THE R22 HS29 UNITS.
L4356
TSA120S4S-G 10
460
SPECIFICATIONS
Model Number
TSA072S4S-Y TSA090S4S-Y TSA090S4S-G TSA120S4S-Y TSA120S4S-G
Nominal Size - Tons
6
7.5
10
Liquid Line (o.d.) -- in. connection (sweat)
(1) 5/8
(1) 5/8
(1) 5/8
Suction Line (o.d.) -- in. connection (sweat)
(1) 1-1/8
(1) 1-1/8
(1) 1-3/8
L
Net face area - sq. ft. Outer Coil
29.3
29.3
29.3
| HVAC
Inner Coil
---
28.4
28.4
Condenser Coil
Tube diameter - in. (mm) & No. of rows
3/8 -1
3/8 - 2
3/8 - 2
Fins per inch
20
20
20
Diameter - in. (mm) & No. of blades
(1)24-3
(1) 24 - 4
(2) 24 - 3
Motor horsepower
(1) 1/3
(1)1/2
(2) 1/3
Condenser Fans
Cfm total air volume
5100
5600
8300
Rpm
1075
1075
1075
Watts
430
580
830
Refrigerant Charge
11 lbs. 0 oz.
16 Ibs. 0 oz.
17Ibs. 0 oz.
ELECTRICAL DATA Model Number
TSA072S4S-Y TSA090S4S-Y TSA090S4S-G TSA120S4S-Y TSA120S4S-G
Line Voltage data - 60 hz - 3 phase
208/230V
208/230V
460V
208/230V
460V
Recommended maximum fuse or circuit breaker size (Amps)
45
50
25
70
40
Minimum circuit ampacity
27
35
17
43
24
Compressors (1)
Rated load amps
19
25
12.2
30.1
16.7
Locked rotor amps
123
164
100
225
114
Condenser Coil Fan Motor (1 phase)
Full load amps (total)
2.4
3
1.5
2.4 (4.8)
1.3 (2.6)
Locked rotor amps
4.7
6
3
4.7 (9.4)
2.4 (4.8)